Originally they were only required at the exterior of the house and by swimming pool equipment.
Are gfci needed in laundry rooms.
Gfci protection is required for 125 volt to 250 volt receptacles supplied by single phase branch circuits rated 150 volts or less to the ground.
Gfci receptacle outlets electrical question.
If the water supply is permanently connected to washing machines in a laundry area does it require a class a gfci protected receptacle.
Gfci receptacles were required in houses starting in 1971.
Now let s refer to nec 2017 section 210 8 for the answer to the gfci portion of our question.
Although the code does not specifically state that a washing machine receptacle has to be gfci the washing machine must have water service and a drain so its location becomes defined as a laundry.
210 8 a 10 all 125v 15a and 20a receptacles installed in laundry areas shall have gfci protection.
If the laundry room does not have a window then an exhaust fan will be required along with a switch.
Because by definition where the washing machine is located becomes the laundry the two phases of this requirement meant that initially a washing.
They should also be installed within six feet of a wet bar.
Otherwise you probably need a a new washing machine or you will be fixing you old one so it runs on a gfci.
So does my washing machine need a gfci outlet.
So in this case yes the washing machine would need to be on a gfci receptacle if in a laundry area which i assume that it would be.
Over the years gfci receptacles have been required in more locations such as garages bathrooms kitchens etc.
The only wiggle room for the washing machine is if it drains into a standpipe drain and there is no sink.
The code mandate was later expanded to include any receptacles in a laundry room in the 2014 nec.
Gfci receptacles are required in bathrooms garages crawl spaces basements laundry rooms and areas where a water source is present.
2005 does require gfci 6 from laundry sinks.
Receptacles within 6 feet of a laundry sink were first required to be gfci protected by the 2005 edition of the national electrical code nec.
See the nec code requirements in the table below for more specific information.
In laundry rooms and utility rooms gfcis should be installed on outlets within six feet of sinks washing machines and water heaters.
Yes as of the 2017 edition of the national electrical code nec any receptacles in a laundry room must be gfci protected.
According to the nec a gfci is required if the power outlet is within 1 8 meter radius from the water source.
When and where are gfci receptacles required.